Is there a difference between LK150AN and Q1150AN

Issue:
Can the LK150AN be used on NQ panels?

Product Line:
Lugs

Environment:
Panelboard, load center, optional lug

Cause:
Can the LK150AN be used in place of the Q1150AN.  Both cost the same and handle the same wire sizes.

Resolution:
The Q1150AN is for use on NQ and NF panel boards.  The Q1 is a slightly different lug that mounts on top of a plate and the plate is what mounts to the neutral.
The LK150AN is for use on QO and Homeline load centers. The LK is a straddle type lug.