Technical FAQs

Ask a Question

What is ULF on the ATS48?

What is ULF on the ATS48?
ATS48, Altistart 49 ,Issue: 
What is ULF on the ATS48?
Product Line:
Altistart 48
All serial numbers
Drive is detecting an under load fault?
ULF is an under load fault.   The fault is caused by parameter settings on the soft starter.  In the PRO menu parameter ULL (Activation of motor under load) enables the under load detection.   Parameter LUL (Motor underload threshold) set the percentage of torque for the underload detection.   Parameter TUL (Motor underload time)Set the time delay before ULL faults when the motor torque falls below LUL threshold.
Was this helpful?
What can we do to improve the information ?