Technical FAQs

Ask a Question

Will an MH36800 fit in a HCP panel?

Issue:
Breaker for I-Line panel

Product Line:
Panelboards

Environment:
I-Line HCP

Cause:
Mounting

Resolution:

 
 
 
 

Neither the MA or MH breakers will fit in the wide side of this I-Line panel. The cam foot has no where to engage the back panel. Use the HCRU or older HCW interior instead.
Was this helpful?
What can we do to improve the information ?