How many HEPD80 protection devices are needed for (2) 200A load centers in my home?

Issue:
How many HEPD80 protection devices are needed for (qty 2) 200A load centers in my home?

Product Line:
Home Surge Protective Device, Surgelogic

Environment:
Surgelogic products, United States

Cause:
Specifications needed for protection of 2 load centers in home
 
Resolution:
If the panels have individual feeds then you will need two separate units.  If they are mounted side by side and one panel has a breaker feeding the other panel - sub fed or thru feed - you can put the SPD in the first panel and it should provide protection to the second panel.