How to determine which option card is installed on the ATV61 or 71 drives?

Issue: 
How to determine which option card is installed on the ATV61 or 71 drives?
 
Product Line:
Altivar 61, Altivar 71
 
Environment:
All Serial numbers
 
Cause:
N/A
 
Resolution:
To determine if an option called is installed on the ATV61/71, go to menu 1.11 in the drives menu enter and find menu option 1 and option 2 this will display the option cards install. 

Troubleshooting tips:
If one of the options 1 or options 2 show an unknown option or  if unknown is displayed. Check the card to see if its seated correctly or try reseating the option card.
If there is problem with one of the option cards and you need to get the part number of the option card that is installed. You can find the VW3AXXXXX part number on the white bar  code on the leg of the option card.
See the image below.