Can I assign a different logic input other than LI1 to run forward ?

Issue:
Can I assign a different logic input other than LI1 to  run forward ?
 
Product Line:
ATV61 ATV71
 
Environment:
All 
 

Cause :
LI1 logic input inoperative

 

Resolution:
No, no other forward assignment in 2 wire configuration. In 3 wire control LI1 is run and LI2 is forward.


 

 