Can you daisy-chain ZSI outputs for Powerpact H, J, L breakers with Powerpact P and R on the same level?

Product Line:
Powerpact H, J, L, P, R

Yes, the ZSI outputs of these breakers can be linked together for bringing a common cable to a ZSI Interface Module, RIM, or upstream Powerpact/Masterpact breaker.