Technical FAQs

Ask a Question

What is the largest ampere size breaker that can be added to a HCP panel ?

Issue:
Largest amp size breaker

Product Line:
Panelboards

Environment:
I-Line

Cause:
Selection of maxium size breaker
 
Resolution:
 
 
 
 

For the HCP the largest branch or main is an 800a due to wire bending space.
Was this helpful?
What can we do to improve the information ?