What are the lug torque specs for 9422TF1

What is the torque spec for 9422TF1

Product Line:
9422 flange mounted disconnect

200A unfused and fused

Customers need to know torque spec for wire binding screw and lug retaining nut

Lug tightening torque for wire binding screw for both the AL and CU lugs is 375 In Lbs.  Tightening torque for the lug retaining nut is 75 In Lbs.

Keywords: operating mechanims, mech, 9422ATF11 9422ATF21 9422TF2 9422TF22 9422ATF12