How is damper control configured on the ATV212 series drive?

Issue:
To check if damper control is configured on the ATV212 series drive.
 
Product Line:
Altivar 212 series drives.
 
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
 
Cause:
Damper control configuration assistance needed with this drive.
 
Resolution:
 
Damper control on the ATV212 drive requires 3 setting to be adjusted.   You need to configure a relay output to control the damper, you need to configure a logic input to monitor the damper status via the damper end switch, and parameter F508 needs to be configured for the type of feedback switch your damper has.  See details from the ATV212 Programming manual below:
 


 
 






 