What is the termination temperature rating for HVL/cc?

Issue:
Installation, Application

Product Line:
INMVP - PRODUCT _ SWITCHGEAR

Environment:
NEMA, UL, ANSI/IEEE C37.20.3, C37.20.4, C37.57, C37.58, CSA 22.2 no.s 31 and 193

Cause:
Proper selection and sizing of conductors.

Resolution:
The lugs and terminations for HVL/cc are rated 90 deg C. Cable rated 105 deg C may be used; however, it will have to be sized as if it were 90 deg C. 