How do you set the line termination resistor on the ATV212 drive set up for Bacnet protocol?

Issue:
How do you set the line termination resistor on the ATV212 drive set up for Bacnet protocol?

Product Line:
Altivar ATV212

Environment:
All

Cause:
Needs to terminate his Bacnet line and wants to know how to set the drive up.

Resolution:
Switch SW103 is the line termination resistance switch to put 120 ohms across the data pins A and B.
 