How do you set up a digital input for a fault reset on the ATV630 Process drive?

Issue:
How do you set up a digital input for a fault reset on the ATV630 Process drive?

Product Line:
Altivar ATV630 ATV650

Environment:
All Process drives

Cause:
Needs to set up a digital input to do a fault reset.
Resolution:
Fault reset via logic input example:
Menu 5 complete settings  enter(ok)
scroll down
Menu 5.11 Error/Warning Handing  enter (ok)
Fault set enter
Fault Reset Assignment
choose DI2  for digital input 2 being the fault reset.
 