What would cause the ATS48 HMI to randomly and continuously cycle through menu selections?

Issue:
What would cause the ATS48 HMI to randomly and continuously cycle through menu selections?

Product Line:
ATS48

Environment:
All

Cause:
HMI display is unstable

Resolution:
Most suspect is a defective control board. Replace the control board, part number VX4G481.