What is the normal operating temperature for the coils in Type S Starters

Issue:
The coil in my 8536S starter seems hot.  What is the normal operating temperature for these coils?

Product Line:
8536S NEMA Starters

Environment:
US Product

Resolution:
Coil temperature rise is defined by NEMA standard 8.3.2 in publication ICS 1-200.  Under this standard, coil temperature is allowed to rise 85C above ambient temperature.

 