How can you put the ATV61 and ATV71 drives in a NET command control mode?

Issue:
How can you put the ATV61 and ATV71 drives in a NET command control mode?

Product Line:
Altivar ATV61 and ATV71 with an Serial communications option card.

Environment:
All

Cause:
The drive is showing Terminal control mode they need to set it up for NET control.

Resolution:
Basic Programming settings will be
Set up your communications card in menu 1.9
Set your Ref 1 1 channel to com card in menu 1.6
Set your Profile to be not separate in men 1.6
or
Set your Profile to be Separate  then CMD switching to a logic input or choose channel reference as com card.

I have attached the ATV61 programming manual to assist if needed.
 