What is the resistance on NEMA size 3, 2 & 3 pole, AC coils?

Issue:
What is the resistance on NEMA size 3, 2 & 3 pole, AC coils?

Product Line:
NEMA Magnetic AC Coils

Environment:
US Product Lines

Cause:
Can not find it in the Digest

Resolution:
At 20 degrees C operating temperature (60 Hz only):

24V = 0.35 Ohms

120V = 8.48 Ohms

208V = 28.7 Ohms

240V = 34.1 Ohms

277V = 49 Ohms

380V = 85 Ohms

480V = 138 Ohms

600V = 261 Ohms