Why is coil part number 31104-400-50 used for all system voltages?

Issue:
Why is coil part number 31104-400-50 used for all system voltages?

Product Line:
9998 Magnetic Coils

Environment:
US Product Lines

Cause:
Can not find it in the Digest

Resolution:
This coil is used for ALL system voltages, because it is powered and controlled by a control module which develops the DC pickup and DC holding voltages.

Ohms = 3.4 to 4.2 (20°C) - If the coil reads outside this range, the coil should be replaced.