Technical FAQs

Ask a Question

How do you set up the underload detection function on the ATV212 drive?

Issue:
How do you set up the underload detection function on the ATV212 drive?

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Needs detect a belt breakage so he wants to monitor underload threshold.

Resolution:
Basic Programming
F------- enter
F610= set to 0 for Relay alarm 
           set to 1 for underload fault
F611= underload level in factory defualt A or amps .. If you change F701 to 0 you can set this as a % of the Drives IN current ratings.
F609= underload bandwidth
F612= underload detect time

Function works as follows
If the motor current drops below the programmed F611 amp value for the duration of the programmed F612 detection time.  The drive will trip on underload fault or alarm depending on F610 setting.



 
Was this helpful?
What can we do to improve the information ?