Technical FAQs

Ask a Question

What is the fuse size for the ATS22 CL1 CL2 control circuit?

Issue:
What is the fuse size needed to protect CL1-CL2 on the ATS22 soft starts? 

Product line:
ATS22, Altistart 22

Environment:
All models (S6 and S6U)

Cause:
The drawings and installation show fuse/overcurrent protection on CL1, but no notes on what size or type of protection to use.

Resolution:
According to our L3 team,  The CL1 - CL2 control voltage input should have a 1A fact acting fuse, or 1A circuit breaker for each ATS22 unit.  This applies to the 120 V and 230 V control supplies (Q, S6 and S6U)



 

Was this helpful?
What can we do to improve the information ?