What happens to Powerlink breakers in the event of a power loss?

Issue:
What happens to Powerlink breakers in the event of a power loss?

Product Line:
Powerlink G3 Lighting Control

Environment:
Commercial Lighitng Control in North America

Cause:

Resolution:
If a Master Panel (Panel with the Powerlink Controller) loses power, then the breakers remain in the state that they were last commanded when the panelboard lost power.   The entire Powerlink subnetwork of slave panels remain in the last state the breakers were commanded as well.

If a Slave Panel loses power, the breakers remain in the state that they were last commanded at the time the panelboard lost power.

If a Master Panel loses power but the Slave Panel does not, the breakers of the Slave Panel will all stay in the state they were last commanded.