What resistor is required for the LX9FJ replacement coils?

Issue:
What resistor is required for the LX9FJ replacement coils?

Product Line:
TeSys F-Line Contactors

Environment:
All Product Lines

Cause:
Can not find it in the Digest

Resolution:

LX9FJ918 48V coil uses resistor DR2SC0047

LX9FJ926 110V coil uses resistor DR2SC0030

LX9FJ927 125V coil uses resistor DR2SC0390

LX9FJ932 220V coil uses resistor DR2SC1200

The LX9FJ938 coils are no longer available.