Can you set up the ATV212 or S-Flex drive to display motor speed in percent?

Issue:
How can you program the ATV212 drive to display speed in percent %?

Product Line:
Altivar ATV21 ATV212 S-flex enclosed

Environment:
All

Cause:
Needs to show percent speed not hz on the main display

Resolution:
you can set F702 to equal 1.666666  this will allow your 60 hz to be displayed as 60 X 1.6666 or 100%




 