Technical FAQs

Ask a Question

Are the 8903L and 8903LX Rated for LED lighting applications?

Issue:
Does Schneider Electric have documentation on LED ratings for the 8903L or 8903LX 30A rated lighting contactors?

Product Line: 
Full Voltage Lighting Contactors NEMA style,

Environment:
8903 line of NEMA Contactors

Cause:
Installation restrictions

Resolution:
As of 2017 Schneider Electric has tested the Class 8903 Type L/LX and Type S NEMA lighting contactors per NEMA'S LED testing standard 4101.  This test specifies procedures up to 16A loads at 120VAC. Our testing was accomplished at 20A, 120VAC and passed with flying colors.

Schneider Electric's NEMA lighting contactors, Class 8903, are LED Ready.
Was this helpful?
What can we do to improve the information ?