Technical FAQs

Ask a Question

Can the FFTK be used to test M2C contacts and the Micrologic trip unit advanced functions and trip history?

Product Line:
Powerpact and Masterpact breakers 

Resolution:
When using the M2CTEST special adapter, all advanced protections, logging of trips, logging of alarms, activation of alarms and incrementing of the contact wear counter are enabled during the secondary injection test.  
This adapter enables trip unit and M2C / M6C functions the FFTK would normally disable and more closely simulating a primary injection test.  
See attached instruction bulletin EAV34309 for more information.
Was this helpful?
What can we do to improve the information ?