Technical FAQs

Ask a Question

How to get trip history out of Powerpact H, J and L frame Micrologic trip units

Issue:
Is there a record of trip history that can be seen on the trip unit screen of Powerpact H, J and L breakers?

Product Line:
Circuit Breakers

Environment:
Powerpact H, J and L frame circuit breakers, with Micrologic Ammeter and Energy Trip Units
5.2A, 6.2A, 5.2E, 6.2E, 5.3A, 6.3A, 5.3E, 6.3E trip units

Resolution:
Trip history is stored in the trip unit, but it is not visible on the trip unit screen.
Trip history can be obtained using the following:
(1) From a Front Display Module FDM121 (if connected to the breaker)
(2) Remotely, using communications
Was this helpful?
What can we do to improve the information ?