What are the limitations for AC coupling XW+

AC Coupling with XW+ Models

The Comments from Escalation state that for AC coupling you can AC couple up to the lessor of (2 X power rating of single XW+) or 48A relay parameter(48*240=11.5kw)

Example:With (2) XW6848+ total power would be 13.6 kw, and with the 48amp transfer relay (48*240=11.5kw)
Answer:The grid tie inverters would have to be set at or less than 11.5kw since 13.6kw is above the 48 amperage parameter.