What are the basic wiring connections for the ATV212 drive?

Customer needs the basic wiring connections for an Altivar 212 drive.

Product line:
ATV212, Altivar 212

All models

Limited wiring details provided with the drive.

The minimum requirements to operate an ATV212 drive are a run command and a speed reference.  Be default from the factory, Terminals F to P24 are the run forward and run permissive input.  VIA to CC is the default speed reference for 0-10V. 

P24 has its own 24VDC power supply, so use a dry contact closure on F to P24. 

**Note these values and assignments can be changed in the Programming.  These are the default settings only, with CNOd = 0 and FNOd = 1.