How do you set the PID feedback assignment( PIF) parameter to AI1 on the ATV12 drives?

Issue:
How do you set the PID feedback assignment( PIF) parameter to AI1 on the ATV12 drives?

Product Line:
Alitivar  ATV12

Environment:
All

Cause:
Needs to set the PIF parameter to AI1 for PID feedback assignment.

Resolution:
IO menu
AII enter
AIIt (AI1) set this for 0 5-vdc, 0 10vdc or 4 to 20mA

CTL menu
Set Ref 1 channel FR1 to AI Virtual 1 ( Command menu)
Set CHCF to SEP
Set Cd1 to Term

FUN menu
PId enter
PIF Set PID feedback assignment to AI1 ( PID Regulator menu)