How do you set the PID feedback assignment( PIF) parameter to AI1 on the ATV12 drives?

Issue:
How do you set the PID feedback assignment( PIF) parameter to AI1 on the ATV12 drives?

Product Line:
Alitivar  ATV12

Environment:
All

Cause:
Needs to set the PIF parameter to AI1 for PID feedback assignment.

Resolution:
Set AI1 to current or 4-20mA ( IO menu)
Set Ref 1 channel FR1 to AI Virtual 1 ( Command menu)
Set PID feedback assignment to AI1 ( PID Regulator menu)