Technical FAQs

Ask a Question

How can you program the ATV21 or ATV212 drive so that you can run the drive without the motor?

Issue:
How can you program the ATV21 or ATV212 drive so that you can run the drive without the motor connected to it?

Product Line:
Altivar ATV21 ATV212 S-Flex enclosed

Environment:
All

Cause:
Needs to test the drive to see if there is a problem with it wants to run the drive open circuit without the motor connected to it.

Resolution:
Programming
Find F----- Enter
Turn off output phase loss F605= 0 (Disable)
Set supply voltage correction F307 to 2 (supply voltage uncorrected).
Now you can disconnect your motor leads and run the drive open circuit to test.
 
Was this helpful?
What can we do to improve the information ?