Is there a lug for a 600A NQ panel that will accept (3) 250 kcmil Aluminum wire per phase

Issue:
Is there a lug for a 600A NQ panel that will accept (3) 250 kcmil Aluminum wire per phase 

Product:
NQ panelboards sold and supported in the USA.

Environment;
Application

Cause:
Selection/product features

Resolution:
Order the NQALM6A lug kit. This kit contains three phase lugs, two neutral lugs and ten mounting screws.  



Yes 80122-254-50