What is the interlock kit to make a reversing pair for the LC1D40A, D50A & D65A?

Needs to interlock a pair of D40A, D50A or D65A

Product Line:
TeSys D Everlink Contactors, limited to D40A, D50A or D65A

Products sold and used in the United States

Use the LAD4CM, without electrical interlock. Alternately the LAD9R3 (which combines both the LAD4CM mechanical interlock and LA9D65A69 set of power connections for reversing contactors for motor contro)l.