What is the short circuit current rating of non-fused general duty safety switches when used down stream from circuit breakers?

Issue:
Product Design Features

Product Line:
General duty non-fused safety switches

Environment:
Short Circuit Current Ratings

Cause:
Application
 
Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating, because it does not contain any over current protection. BUT any brand of circuit breaker or fuse not exceeding the ampere rating of the switch, may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available. Evaluation of non-fused switches used in conjuction with molded case circuit breakers has NOT been performed.