Technical FAQs

Ask a Question

What is the power consumption (VA) of the M2C Programmable Contact Module Kit S64273?

Product Line:
Masterpact, Powerpact, Micrologic

Resolution:
The M2C requires an external 24 Vdc power supply and draws 100 mA (2.4 VA power consumption).

The minimum contact load is 100 mA at 24 Vdc, and maximum current and voltage rating for the contacts is shown in the table below.
 
Minimum Load 100 mA/24 V
Breaking Capacity at a Power Factor (p.f.) of 0.7 240 Vac 5.0 A
380 Vac 3.0 A
24 VDC 1800 mA
48 VDC 1500 mA
125 VDC 400 mA
250 VDC 150 mA
Was this helpful?
What can we do to improve the information ?