Can the MotorLogic solid state relays be used on single phase applications?

Product Line:
9065 solid state relays series F

US Product

Older MotorLogic solid state overload relays could not be used with single phase applications, but series F units can. 

Yes, however only Series F and newer. These units can be used with single phase applications by looping one of the wires so that it passes through all three CTs in the overload.  See page 8 of the attached instruction sheet for an example.