Will the ATV61 and ATV71 drives have a built in ON delay timer for the logic inputs?

Issue:
Customer needs to delay the run command after LI1 closes. 

Product line:
Altivar 61, ATV61, Altivar 71, ATV71

Environment:
All models, all serial numbers.

Cause:
n/a

Resolution:
Under Menu 1.5 Inputs Outputs Config go to LI1 Configuration > LI1  On Delay. 
     The default setting for this parameter is 0 ms.  It can be changed from 0 to 200 ms. 

The time delay function is available on all the logic inputs.