Can a 2-pole CAFI, GFI or EPD breaker be used to feed (2) 120V single-pole circuits that share a common neutral? (shared neutral)

Issue:
Can a 2-pole CAFI, GFI or EPD breaker be used to feed (2) 120V single-pole circuits that share a common neutral?

Product Line:
QO, QOB and HOM Circuit Breakers

Environment:
Applies to 2-pole QO, QOB and HOM circuit breakers with suffix CAFI, GFI or EPD.

Cause:
Two 120V circuits are fed with a multi-wire conductor, consisting of 2 hot wires, 1 neutral wire, and 1 ground wire. The two 120V circuits are sharing the neutral wire.

Resolution:
Yes, 2-pole CAFI, GFI or EPD circuit breakers can be used to feed two single pole 120Vac circuits that share a common neutral. This situation often occurs when a multi-wire conductor is used to feed the 2 circuits. These may be applied on the following systems:
2p CAFI (use on 120/240V system; not for use on 208Y/120V system)
2p GFI (use on 120/240V as well as 208Y/120V systems)
2p EPD (use on 120/240V as well as 208Y/120V systems)