What parameter enables Catch on the Fly on the ATV21 and ATV212 series drives and how is it configured?

Issue:
What parameter enables Catch on the Fly on the ATV21 and ATV212 drives and how is it configured?

Product Line:
ATV21 and ATV212 drives.

Environment:
All models, All serial numbers.

Cause:
Clarification of function and how to configure it is needed.

Resolution:

Parameter F301 is used to configure the Catch on the Fly function. It has 5 possible settings:

0 : Disabled
1 : Enabled after brief power loss
2: Enabled after run permissive is restored
3: Enabled after a brief power loss or when run permissive is restored.
4: Enabled at every startup.
 