Is there a lug able to accept (3) 600 kcmil wire for a PTPJ36120G Busplug ?

 
Issue:
Is there a lug available that will be able to accept (3) 600 kcmil wire/ per phase, for a PTPJ36120G Busplug ?

Product Line:
I Line Busway

Environment:
Retrofitting Breaker lugs

Cause:
Wire Bending restrictions

Resolution:
AL1200P7KU Lug kit is able to accept (3) 600 kcmil wire and is not in violation of NEC wire bending restrictions  