Is the Canadian Load Center Catalog number QO8L100RB Service Entrance Rated?

Load Center Ratings 

Product Line:
Canadian QO Load centers

Load Center Application 

Service Entrance Rating

The Canadian Electric Code requires load centers for Service Entrance Applications to be a Main Breaker, to have the bonding screw factory installed and a Service Barrier that restricts any load wiring to exit or enter the Service Area(or top endwall) of the load center. So the QO8L100RB is NOT Service Entrance Rated.