How can you convert a Main breaker NQ442L2C panel to Main lug and keep the same MH50 box ?

Issue:
How can you convert a Main breaker NQ442L2C panel to Main lug and keep the same MH50 box ?

Product Line:
NQ Panelboards

Environment:
Conduit piped already into MH 50 box

Cause:
Change from Main breaker to Main lug Panelboard after installation of box

Resolution:
1) Remove the Main breaker kit and install a NQALM2 Main lug kit .

2) Install a 12" rail extension NQ12RDE kit to the Mains end of interior, and use the Blank Deadfront provided in the extension kit to cover Main lugs  



 