Can a Square D/Schneider Electric Sealed Resin Epoxy Encapsulated Transformer with a style A, B, or C enclosure be floor mounted?

Issue:
Can a Square D/Schneider Electric Sealed Resin Epoxy Encapsulated Transformer with a style A, B, or C enclosure be floor mounted?

Product Line:
Epoxy Encapsulated Transformers

Environment:
Class 7400

Cause:
Mounting/Installation

Resolution:
No. Schneider does not have a floor mounting bracket. The Epoxy Encapsulated transformers require a minimum of 12" clearance from all directions for cooling. This includes the bottom.
 