Technical FAQs

Ask a Question

How can you read over modbus if the ATV61 or ATV71 drive is in local or remote control mode with the F4 function key?

Issue:
How can you read over modbus if the ATV61 or ATV71 drive is in local or remote control mode with the F4 function key?

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Needs to know if the F4 function key is in local or remote mode.

Resolution:
I suggested he monitor Address 8441 or 8442 bit 2 to show graphic display command or reference.

This bit 2 will go high when in local HMI mode.
 

Was this helpful?
What can we do to improve the information ?