Technical FAQs

Ask a Question

Why does the drive says "rdy" after the run command is given to LI1?

Issue:
Drive will not start after the run command is given to LI1.

Product Line:
ATV312

Environment:
All

Cause:
Will not turn on motor

Resolution:
"rdy " on the HMI display means no run command has been issued.
Measure voltage between LI1 and com terminals verify +24Vdc is present with run command
Check the wiring between LI1 and +24Vdc ( customer switch )
Verify the programming is setup for terminal control ( CCS and Cd1 menu CtL)
Verify tCC settings for 2wire / 3wire matches the run command wiring. 
Verify the drive is "not" in local mode ( push the green run button on the HMI )
Was this helpful?
What can we do to improve the information ?