Technical FAQs

Ask a Question

How do you set up the ATV61 drive to be used with the VW3A3314 Apogee P1 option card?

Issue:
How do you set up the ATV61 drive to be used with the VW3A3314 Apogee P1 option card?

Product Line:
Altivar ATV61 with VW3A3314 option card.

Environment:
All

Cause:
Needs setup assistance with the ATV61 and Apogee P1 card.

Resolution:
Card connector Pin outs

Contact B= (+) signal
Contact A= (-) signal
Contact GND= (GND)
Contact SCR= (Shield)

Programming Drive  ( You must Power cycle after changing any of the Menu 1.9 coms parameter settings)
Menu 1.9- Communications (CON)
Address range is 0-99  (Choose your address)
Baud rate: Choose between 4800 to 76800
Network time out = range is 2 to 60 seconds (Choose your network time out)

Menu 1.6 Command menu
Controlling the drive over the network
Ref 1 = Com card
Profile is Not separate
Point # 24 (LDO  table) is your start command for CMD  (writing a 1 will start 0 will stop)
Point # 60 (LAO table) is your input speed reference 1 in %
Note: If the drive will not start with writing a 1 to Point #24 try writing a 0 to #24 1st then writing a 1.

Reading data only from the drive.
Ref 1 AI1
Profile not separate
Point #03= freq output in hz
Point #05= speed output in rpms
Point # 06= Motor current
Point # 07= Motor Torque
Point # 08= Motor Power
Point # 09 = Drive Temp
There are other values that you can read in the LAI table see the attached document for information.

Was this helpful?
What can we do to improve the information ?