What Solid Neutral Kit can be used with the L600AWK?

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Environment:
Selection

Cause:
Selection

Resolution:
There are several options for solid neutral kits for use with the L600AWK:

SN400LA for up to 400A applications. Accepts AL or CU conductors.
SNC400LX for up to 400A applications. Accepts only CU conductors.
SN1000MA for up to 600A applications. Accepts AL or CU conductors.
SNC800LX for up to 600A applications. Accepts only CU conductors.

NOTE: The L600AWK will not accept the L Frame PowerPact breaker with the LSIG function due to no Neutral CT capability. None of the neutrals listed above will accept a Neutral CT. Expected availability of an acceptable Neutral Assembly for the Neutral CT is late 4th Quarter, 2016

NOTE: No 200% Neutral is offered.