Does Square D offer an enclosure for the L Frame PowerPact Circuit Breakers?

Product Availability

Product Line:
Circuit Breaker Enclosure



Yes, the enclosures for the new PowerPact L Frame Circuit Breakers or Motor Protector Circuit Breakers are part numbers L600AWK , L600AWKVW (this enclosure has a viewing window for trip unit viewing) and L600AWKMC(this enclosure is for the molded case switches ONLY). The enclosures are listed and labeled as Rainproof and Dusttight and suitable for  NEMA Type 1, 3, 3R, 5 or 12 installations. When used in an outdoor, rainproof application, remove the drain screw in the bottom endwall and discard.

1) The L600AWK will not accept the L Frame PowerPact breaker with the LSIG function due to no Neutral CT capability.
2) If using a  third-party manufacturer for enclosure, minimum dimensions for LD, LG, LJ, and LL breakers are 35.48 x 12.00 x 4.45 in., or (901 x 305 x 113 mm).
3) If using a  third-party manufacturer for enclosure, minimum dimensions for LR breakers are 40.5 x 13.75 x 4.33 in., or (1030 x 350 x 110 mm).