How do you set up preset speeds on the ATV32 drive?

Issue:
How do you set up preset speeds on the ATV32 drive?

Product Line:
Altivar ATV32

Environment:
All

Cause:
Preset speeds for controlling the speed

Resolution:
FULL menu enter
FUn menu enter
PSS menu enter
PS2= 2 preset speeds assign to your logic input
PS4= 4 preset speeds assign to your logic input
PS8= 8 preset speeds assign to your logic input
PS16= 16 preset speeds assign to your logic input

Preset speed values are  SP2 thru SP16 in hz.

Example 3 speeds you will need to assign 4 preset speeds
LI4  preset 2 preset speeds
LI5 preset 4  preset speeds

Logic will be as follows
LI4=0 LI5=0  Drive runs at low speed for follows your analog input.
LI4=1 LI5=0 Drive runs at speed 2
LI4=0 LI5=1 Drive runs at speed 3
LI4=1 LI5=1 Drive runs at speed 4





 