Can the remote racking devices (NTMPRRT and NWMPRRT) for Masterpact NT and NW be used on IEC breakers and cradles?

Issue:
Can the remote racking devices (NTMPRRT and NWMPRRT) for Masterpact NT and NW be used on IEC breakers and cradles?

Product Line:
Masterpact NT and NW

Environment:
IEC

Cause:
Application question

Resolution:
Yes, the racking devices can be used on IEC cradles as well as UL and ANSI versions.