Can you use the same P24 vdc signal from one ATV212 drive to start another ATV212 drive?

Issue:
Can you use the same P24 vdc signal from one ATV212 drive to start another ATV212 drive?

Product Line:
Altivar ATV212

Environment:
All

Cause:
Needs to use only one power signal to start two drives.

Resolution:
You will need to jumper the CC terminals together then you can use the same P24 vdc signal for each logic input F for starting.
 